Chapter 7
Programming Parameters

7-16

Parameter 100 – Logic Status [Logic Status]

Internal Units : None
Programming Terminal units : Bit Field
Description : This is a word of status data that indicates conditions
within the Drive in boolean logic. Where a bit is set to 1, the
corresponding condition in the drive is true, otherwise the condition is
false. The bits in the Logic Status word are defined as:

Fault Field 0
Fault Field 1
Active Logic Command 0
Active Logic Command 1
Contactor Closed
Drive Running
Running Reverse
Ready
At Current Limit
At Set Speed
At Zero Speed
At Speed 1
At Speed 2
At Speed 3
At Speed 4
At Speed 5

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

N O T C H A N G E A B L E

Bit #

DHT REF. BITS

DEFINITIONS

0
1

2
3
4
5

6
7
8
9

10

11

12
13

14
15

Fault Field 0, 1 (Bits 0, 1) : This 2-bit field denotes the fault status of
the Drive as follows:

Flt. Fld. 1

0
0
1
1

Flt. Fld. 0

0
1
0
1

DEFINITION

No Fault
Warning Fault
Soft Fault
Hard Fault

Active Logic Command 0,1 (Bits 2,3) : This 2-bit field denotes the
logic command the Drive is acting upon as follows:

Logic CMD 1

0
1
1

Logic CMD. 0

1
0
1

DEFINITION

Parameter 150
Parameter 151
Parameter 152