Chapter 8
Start–Up

8-6

4. Record the following DC voltage measurements in Tables 8.E to 8.G.
If any voltage measurement is incorrect, refer to the Troubleshooting

manual for guidelines.

+5 +/– 0.15VDC measured at TP 51 (+) with respect to TP 52 (–)
on the Main Control Board.

+12 +/–0.48VDC measured at TP 55 (+) with respect to TP57 (–)
on the Main Control Board.

–12 +/– 0.48VDC measured at TP56 (+) with respect to TP57 (–)
on the Main Control Board.

+5 +/– 0.15VDC measured at TP58 (+) with respect to TP53 (–) on
the Main Control Board.

+12 +/– 0.48VDC measured at TP54 (+) with respect to TP53 (–)
on the Main Control Board.

+24 +/– 6VDC is measured at the Power Stage Interface (PSI) as
outlined in Table 8.E.

Table 8.D
24VDC Voltage Measurements

Horsepower

1 – 30
2 – 60

40 – 100
75 – 200

125 – 300
250 – 600

Drive Voltage

24VDC Measurement Points

230VAC
460VAC

230VAC
460VAC

230VAC
460VAC

TP25 (+) with respect to TP6(+)

TP5 (+) with respect to TP23 (–)

TP6 (+) with respect to TP3 (–)

Table 8.E
Voltage Measurements, 1-30HP 230V and 2-60HP 460V Series B

Test Points

AC VOLTAGES:
L1 to L2
L2 to L3
L3 to L1
TB1-1 to TB1-2
TB2-2 to TB2-3

Rated AC Input
Rated AC Input
Rated AC Input
Rated AC Field Input
115VAC +/–10%

Expected Voltage

Measured Voltage

MAIN CONTROL BOARD:
TP51 to TP52
TP55 to TP57
TP56 to TP57
TP58 to TP53
TP54 to TP53

+5 +/– 0.15 VDC
+12 +/– 0.48 VDC
–12 +/– 0.48 VDC
+5 +/– 0.15 VDC
+12 +/– 0.48 VDC

PSI BOARD:
TP25 to TP6

+24 +/– 6 VDC

Important:

Refer to Chapter 1, “Publication References” for manuals
describing larger horsepower and current ratings at other line
voltages.

Advertising