Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual

Page 241

Advertising
background image

Chapter 7
Programming Parameters

7-75

Parameter 910 – Trend 1 Operand Parameter X [Tr 1 Opnd X
Param]

Internal units : None
Programming Terminal units: None
Minimum Value: 1
Maximum Value: 947
Default Value: 100
Description: This parameter specifies the first of two parameter
numbers for the trend trigger evaluation. The data value for the
entered parameter number is used in the trigger evaluation.

Parameter 911 – Trend 1 Operand Parameter Y [ Tr 1 Opnd Y
Param]

Internal units : None
Programming Terminal units: None
Minimum Value: 1
Maximum Value: 947
Default Value: 904
Description: This parameter specifies the second of two parameter
numbers used for the trend trigger evaluation. The data value for the
entered parameter number is used in the trigger evaluation.

Parameter 912 – Trend 1 Operator [Tr 1 Operator]

Internal units : None
Programming Terminal units: None
Minimum Value: 1
Maximum Value: 8
Default Value: 5
Description: This parameter specifies the operator used in Parameters
910 and 911 for the trend trigger evaluation. The available operators
are:

1 – Greater Than

(.GT.)

2 – Less Than

(.LT.)

3 – Equals

(.EQ.)

4 – Not Equals

(.NE.)

5 – Logical AND

(.AND.)

6 – Logical NAND

(.NAND.)

7 – Logical OR

(.OR.)

8 – Logical NOR

(.NOR.)

Advertising