Chapter 8
Start–Up

8-14

Adapter Parameters

In order to operate the drive from external control devices it first must be
configured by linking Source Parameters to Sink Parameters as described
in the Configuration section of Chapter 5. The drive can be controlled by
either discrete I/O devices using the Discrete or Digital Reference Adapter
Board, or an Allen-Bradley PLC3 or 5 using the Node Adapter Board or
the Multi-Communication Adapter. The 1395 is factory preconfigured as
shown in Tables 8.O and 8.P. The user has the flexibility of reconfiguring
the drive to tailor it to his specific requirement. Refer to the specific
Adapter manual for all configuration and parameter information.

Table 8.O
Drive Pre-Configuration Table — Discrete Adapter

Link

1
2
3
4
5
6
7
8
9

10

11

12
13
14
15
16
17
18

19*
20*

Sink Parameter

151
161
154
156
450
451
452
453
454

152
250

Linked to Source Parm

400
401
403
404
100
106

118
112

105

200
100