Application setup – Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual

Page 266

Advertising
background image

Chapter 8
Start–Up

8-22

3. Set KI, KP for the CEMF regulator (Parameters 672, 673), to their

default value.

4. Set Parameter 612, the rated motor field current to the

actual value, referring to the motor nameplate data.

IMPORTANT: The Drive start command must be true for the entire
time the test is being performed. If a stop command is issued anytime
during the test, the motor will stop and the test will be aborted. Check
Parameter 624 (maintain start) to determine if the start command is
latched or momentary.

!

ATTENTION: The drive Start command must be true for the en-
tire time the test is being performed. If a stop command is issued
anytime during the test, the motor will stop and the test will be
aborted. Check Parameter 624 (maintain start) to determine if the
start command is latched or momentary.

5. Start the drive and run it at the same speed as specified by Parameter

699.

6. Select the Field Flux Tune option (Drive Setup/Autotune/Vel

Tune) using the program terminal.

7. The Field Flux tuning will begin. It takes approximately 5 to 60

seconds for the test to complete, at which time the program terminal
will indicate that the test has been completed and the option of
saving this information in EEPROM can be executed.

Application Setup

NOTE: Prior to doing any further application specific programming, the
application Parameters 607, 608, 663 and 664, if not previously
programmed, will have to be programmed for their final value.

There are several parameters associated with the use of the drive for
specific applications. At this point, the basic drive control has been tuned
for simple speed control. If it is desired to operate the drive using one of
the optional functions, refer to Chapter 7 for a description of the
parameters associated with these functions. In addition to set up of the
drive parameters associated with these functions, it is also necessary to
verify correct configuration of the Source to Sink parameters for the
external control device being used to control the drive for the specific
application. Refer to the appropriate adapter board Instruction Manual for
a description of how to use the adapter board and how to interface the
adapter board to the drive to command various drive functions.

Once the drive has been fully tuned and configured:

1. Record the values of all parameters in the Parameter Table located in
Chapter 9.

2. Use the EEPROM mode in the Programming Terminal to save all

parameters in EEPROM.

Advertising