Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual

Page 165

Advertising
background image

Chapter 6
Installation

6-41

Table 6.R
230VAC Input –Armature Current Ratings

.75KW/1HP

1.2KW/1.5HP

1.5KW/2HP
2.2KW/3HP
3.7KW/5HP

5.6KW/7.5HP

7.5KW/10HP

11.2KW/15HP

15KW/20HP

18.7KW/25HP
22.4KW/30HP
29.9KW/40HP
37.3KW/50HP
44.8KW/60HP

56KW/75HP

74.6KW/100HP
93.3KW/125HP

112KW/150HP

149.2KW/200HP
186.5KW/250HP
223.8KW/300HP

Power Output

AC Input

230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

3.85

5.4
7.0

10.0
16.4
23.7
31.0
45.0
65.3
80.0
89.8

135.3
168.0
188.0
233.3
302.7

416
497
591
810
864

ARMATURE

Volts

Max A

DC Output

Volts

Max A

240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240
240

4.7
6.6
8.5

12.2

20
29
38
55
80
98

110

140
180
210
260
345
472
564
670
918
980

AC Input

230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230

10
10
10
10
10
10
10
10
10
10
10
20
20
20
20
20
40
40
40
40
40

FIELD

Volts

Max A

DC Output

Volts

Max A

150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

10
10
10
10
10
10
10
10
10
10
10
10
20
20
20
20
20
40
40
40
40

Advertising