Chapter 8
Start–Up

8-11

Table 8.J
Rated Fld Brdg I Settings (Parameter 616)

J1 Jumper

1
2
3
4

1 – 30 HP, 240VDC
2 – 60 HP, 500VDC

10.6

4.6
2.1
0.6

21.2
9.2
4.2
1.2

40 – 100 HP, 240VDC
75 – 200 HP, 500VDC

125 – 300 HP, 240VDC
250 – 600 HP, 500VDC

42.2
18.4
8.7
2.4

Series B

Series A

Series B MKVA

Table 8.K
Basic Parameters — Feedback Scaling

Parm

739

740

Parameter Name

K Arm Volts

K AC Volts

Numerical value used to scale the armature voltage
feedback. Values to be entered at this time are:
6414 = for 150 – 300 rated arm voltage
12321 = for 300 – 850 rated arm voltage

Description

Numerical value used to scale the incoming AC line
voltage feedback. Values to be entered at this time
are:
3872 = for 150 – 300 rated AC line voltage
7473 = for 300 – 690 rated AC line voltage

Table 8.K.A
Bridge Switch Delay Setting

Parm

744

Parameter Name

Bridge Switch Delay

Normal Applications (for armature time constants
in range of 1 to 100 mS) value should be set to 0.
Non–Zero Values will effect the bandwidth of the
drive.

Description

– High Inductance applications (Armature time

constants greater than 100mS) value needs to be
adjusted according to the parameter description
found in Chapter 7.