Armature current ratings – Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual
Page 164
Chapter 6
Installation
6-40
Node Adapter Board
The Node Adapter Board is connected to Microbus Port B and is not
preconfigured. Refer to the Node Adapter manual for configuration and
installation information.
Multi-Communication Adapter Board
The Multi-Communication Board is not preconfigured. Refer to the
Multi-Communication Adapter manual for configuration and installation
information.
Table 6.P
Terminal Torque Values
Terminals
L1 – L3
AC Input
Amps
Wire
Range
Torque
In. – Lbs.
L1 – L3
2.9 – 45.7
4 – 14
45
–
46.5 – 89.8
2 – 8
50
TB1
14 Max.
5
TB2
22 – 12
5
TB3
22 – 10
6.2
TB4
22 – 12
6.2
Table 6.Q
Terminal Torque Values
Armature
Amps
Wire Range
of Lug
Torque
In. - Lbs.
3.6 – 56
4 – 14
45
57 – 80
2 – 8
50
81 – 180
4/0 – 2
250
*141 – 345
250 MCM – 6
275
*2 wires per lug
Armature Current Ratings
The following tables provide nameplate data information to help you size
wires during installation.