Hardware Description
40 – 100 HP, 230VAC

75 – 200 HP, 460VAC

3-7

Control Boards

Feedback Board – Figure 3.5 illustrates the major hardware points on the
board. The primary function of the board is to provide scaling and transfer
of feedback signals coming from power bridge devices being sent to the
Power Stage Interface and eventually to the Main Control Board.

Figure 3.5
Feedback Board (A1) Overview

TB2

MFG Revision No.

Spare Part Kit No.

Connection for AC current
feedback burden resistor
(Factory Installed)

1

2

3

1

4

TB1

J2

TB3

Л

Л

5

6

7

8

9

11

13

15

17

18

20

23

J1

3

2

4

Connection for DC current
feedback burden resistor
(Factory Installed)

From DC

Current

Feedback

Sensor TD1

20 VAC

from

1 PT

AC Current

Feedback from

CTs ACT–1 & 2

Field Current

Feedback from

FCT

3 Phase Incom-

ing AC Line

voltage Feed-

back

From Heatsink

Thermoswitch

HST

DC Armature Volt-

age Feedback

Connection to Power
Stage Interface

Jumper Selection

for Field Current

Feedback Scaling

(By User At Start-Up)

Table 3.A
Feedback Board Jumpers (see Table 8.J)

J1

Jumper

Position

40 – 100 HP 240 VDC
75 – 200 HP 500 VDC

Field Current Range

9.1 – 21.2 ADC

4.1 – 9.2 ADC

1.1 – 4.2 ADC

0.65 – 1.2 ADC

1

2

3

4