Rockwell Automation 1395 Digital DC Drive FRN 5-10.10/9.30 User Manual

Page 148

Advertising
background image

Chapter 6
Installation

6-24

The voltage used must be the same as the voltage supplied for the
motor thermostat input.

IMPORTANT: The 24VDC provided at TB3-11 and 12 must only be
used for the 24VDC ECOAST circuit.

Figure 6.13
115VAC Input and Contactor Control Connections –
1 to 30 HP, 230VAC; 2–60HP, 460VAC

K3

K

M1

PR

M

A1

A2

A1

A2

Armature

Bridge

TB2

3

4

5

1

115V AC

Fuse

Optional
External

Control Con-

tacts

230 or

460VAC

F3

2

6

7

115 VAC

115 VAC Common

See Step

8

PSI/Switcher Board

1395

M1–X

CVERIFY

To ECOAST

Line

Reactor

or

Isolation

Transformer

L1

L2
L3

AC

Supply

TE

PE

5. Wire External drive Ready Indicator. Terminals TB3-7 and 8 provide

connection to the output contact of the Ready/Fault relay located on the
Power Stage Interface Board. The contacts are rated for 1A at 24VDC
or 0.6A at 115VAC.

6. Wire 115VAC Supply Voltage. It is recommended that the user ground

the 115V secondary of the transformer. The drive Does Not derive its
own control voltage. Therefore, 115VAC must be supplied to the drive
from an external source. A control transformer having a primary of
230V or 460V, based on the drive rating, and a secondary of 115V is
recommended. Primary and secondary must be fused to meet NEC
code. Fuse type FRN and FRS are recommended.

Terminal Connections and VA loads for the different ratings are
outlined in Table 6.N.