Standard Control I/O Checks

The ECOAST Stop and Reset/Normal Stop inputs are supplied as basic
drive inputs. Verify the proper operation of these inputs using the
following steps. If an input does not produce the expected results, verify
correct operation of the appropriate power supply.

1. Apply power to the Drive.

2. If a 24VDC ECOAST stop circuit is used, measure the voltage from

TB3 – 11 to 9 with the ECOAST stop contact open and closed. With
the contact closed, the voltage should be 0VDC. With the contact open,
the voltage should be 24VDC.

3. If a 115VAC ECOAST stop circuit is used, measure the voltage from

TB3 – 4 to 5 with the ECOAST stop contact open and closed. With the
contact closed, the voltage should be 0VAC. With the contact open, the
voltage should be 115VAC.

4. If a 24VDC Reset circuit is used, measure the voltage from TB3 – 1 to

3 with the reset contact open and closed. With the contact closed, the
voltage should be +24VDC. With the contact open, the voltage should
be 0VDC.

5. If a 115VAC Reset circuit is used, measure the voltage from TB3 – 1 to

3 with the reset contact open and closed. With the contact closed, the
voltage should be 115 VAC. With the contact open, the voltage should
be 0VAC.

Parameter Programming Procedures

All drives are shipped preconfigured. Before making any changes review
Chapters 5 and 6. Parameter values are changed using the Parameter mode
in the Drive Programming Terminal. Before beginning any changes,
become thoroughly familiar with the Programming Terminal and its
manual.

To match the Drive control to a specific application, several setup
parameters must be scaled for feedback and other applications. A
description of each of these parameters is provided in Chapter 7 of this
manual. Some of the information previously recorded in Table 8.A will be
required for proper scaling of parameters.

Units of measure for all parameters listed in this section are in terms of
Programming Terminal units.

Before starting this procedure, make certain that the ECOAST input is
locked in the open state. The DC contactor must remain open while the
following parameter setup is being performed.

Parameter Explanations:
Basic Parameters: Tailor the motor to the drive.
Set-Up Parameters: Used for calibration, scaling and special functions.
Speed Reference Parameters: Define the source for the drive speed
command.
Input Parameters: Accept information from sources outside the drive.
Adapter Board Parameters: Define the signals for the specific
applications.