Specifications

NOTE: In order to remain CE and CTick compliant, the SCANport
cable length may not exceed 30 m (98.4 ft.).

NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in
which case supplementary mitigation measures may be required.

Environmental

Temperature

Operating
Storage

-10 to 50

° C (14 to 149° F)

-40 to 85

° C (-40 to 185° F)

Relative Humidity

5 to 95% non-condensing

Atmosphere

Important: Module must not be installed in an area where
the ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the module is not going to be installed for a
period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.

Shock

Operational

Non-Operational

30g, 11 ms (DIN Rail Mount)
50g, 11 ms (Panel Mount)

30g, 11 ms (DIN Rail Mount)
50g, 11 ms (Panel Mount)

Vibration

Operational
Non-Operational

2.5g, 5 to 2000 Hz
5.0g, 5 to 2000 Hz

Regulatory Compliance

UL

UL508C

cUL

CAN / CSA C22.2 No. 14-M91

CE

EN50178 and EN61800-3

CTick

EN61800-3