Troubleshooting

7-3

MOD Status Indicator

Status

Cause

Corrective Action

Off

The module is not powered.

• Securely connect the module to the drive using a

1202-Cxx Communication cable.

• Apply power to the module.

Flashing Red

The module has failed the
firmware test.

The module is being flash
upgraded.

• Clear faults in the module.
• Cycle power to the drive and/or module.
• If cycling power does not correct the problem, the

parameter settings may have been corrupted.
Reset defaults and reconfigure the module.

• If resetting defaults does not correct the problem,

flash the module with the latest firmware release.

Solid Red

The module has failed the
hardware test.

• Cycle power to the module.
• Replace the module.

Flashing Green The module is operational,

but is not transferring I/O
data.

• Place the controller in RUN mode.
• Program the controller to recognize and transmit

I/O to the module.

• Configure the module for the program in the

controller.

• Normal behavior if no SCANport I/O is enabled.

Solid Green

The module is operational
and transferring I/O data.

No action required.

Flashing Red/
Green

The module is in boot mode.

• Flash the module with the latest firmware release

over the serial port.

If Port and Net A are also
flashing Red/Green, then the
module is performing a
self-test.

• No action required.