10 using i/o messaging – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 62

Advertising
background image

5-10

Using I/O Messaging

Figure 5.5 Example ControlLogix Ladder Logic Program for I/O Messaging (Cont.)

This rung displays the Feedback word from the 1305 drive. Note that the value is in an engineering unit, where "32,767"

equals the Parameter 19 [Maximum Freq] value and "0" equals 0 Hz. The relationship is linear. For example, if Parameter

19 = 60 Hz (default setting), then:

32,767 = 60 Hz

16,384 = 30 Hz

8,192 = 15 Hz

4,096 = 7.5 Hz

0 = 0 Hz (etc.)

6

Move

Source AB1305_Drive:I.Data[3]

16384

Dest

Feedback

16384

MOV

1305

Feedback

This rung displays the Feedback word from the 1305 drive. Note that the value is in an engineering unit, where "32,767"

equals the Parameter 19 [Maximum Freq] value and "0" equals 0 Hz. The relationship is linear. For example, if Parameter

19 = 60 Hz (default setting), then:

32,767 = 60 Hz

16,384 = 30 Hz

8,192 = 15 Hz

4,096 = 7.5 Hz

0 = 0 Hz (etc.)

Datalink data from drive. This rung is used for display purposes only. The AB1305_Drive:I.Data[*] tags could be used

directly elsewhere in the ladder program.

AB1305_Drive:I.Data[4] = Datalink A1 1305 Pr.111 = 7 [Accel Time 1]

AB1305_Drive:I.Data[5] = Datalink A2 1305 Pr.112 = 8 [Decel Time 1]

AB1305_Drive:I.Data[6] = Datalink B1 1305 Pr.113 = 10 [Stop Select]

AB1305_Drive:I.Data[7] = Datalink B2 1305 Pr.114 = 24 [Jog Frequency]

AB1305_Drive:I.Data[8] = Datalink C1 1305 Pr.115 = 27 [Preset Freq 1]

AB1305_Drive:I.Data[9] = Datalink C2 1305 Pr.116 = 28 [Preset Freq 2]

AB1305_Drive:I.Data[10] = Datalink D1 1305 Pr.117 = 29 [Preset Freq 3]

AB1305_Drive:I.Data[11] = Datalink D2 1305 Pr.118 = 73 [Preset Freq 4]

7

Copy File

Source AB1305_Drive:I.Data[4]

Dest

Datalinks_from_Drive[0]

Length

8

COP

Pr.7 Accel Time 1

Datalink data from drive. This rung is used for display purposes only. The AB1305_Drive:I.Data[*] tags could be used

directly elsewhere in the ladder program.

AB1305_Drive:I.Data[4] = Datalink A1 1305 Pr.111 = 7 [Accel Time 1]

AB1305_Drive:I.Data[5] = Datalink A2 1305 Pr.112 = 8 [Decel Time 1]

AB1305_Drive:I.Data[6] = Datalink B1 1305 Pr.113 = 10 [Stop Select]

AB1305_Drive:I.Data[7] = Datalink B2 1305 Pr.114 = 24 [Jog Frequency]

AB1305_Drive:I.Data[8] = Datalink C1 1305 Pr.115 = 27 [Preset Freq 1]

AB1305_Drive:I.Data[9] = Datalink C2 1305 Pr.116 = 28 [Preset Freq 2]

AB1305_Drive:I.Data[10] = Datalink D1 1305 Pr.117 = 29 [Preset Freq 3]

AB1305_Drive:I.Data[11] = Datalink D2 1305 Pr.118 = 73 [Preset Freq 4]

Logic Command bit control rungs are provided for display purposes only. The AB1305_Drive:O.Data[0].x bits could be used

directly elsewhere in the ladder program.

8

Stop_Command

1305

Logic Command

STOP

AB1305_Drive:O.Data[0].0

Logic Command bit control rungs are provided for display purposes only. The AB1305_Drive:O.Data[0].x bits could be used

directly elsewhere in the ladder program.

9

Start_Command

1305

Logic Command

START

AB1305_Drive:O.Data[0].1

10

ClearFault_Command

1305

Logic Command

CLEAR FAULTS

AB1305_Drive:O.Data[0].3