Supported Emulated Block Transfer Commands

F-5

Figure F.3 Parameter Value Write Message Structure

Message Operation

Parameter Value Write sends a new value to the specified parameter.
The value must be in device units. Units for each parameter are listed in
the device manual.

If an error has occurred, word 1 of the response returns a value of
–31999, and word 3 contains a status code.

Example

In this example, a value of 4096 was sent to Parameter 20. 4096 is in
drive units and indicates a value of 100% Drive Rated Volts, as defined
in P147, Drive Rated Volts.

Data File Format

* Example only — These values vary depending on parameters and products.

Header Word 1

Data Word 2

PLC Request

Message Length

PLC Decimal Value

–31999

Parameter Number

Drive Response

4

Data Word 3

Parameter Data

Header

Word 0

Header

Word 1

Data

Word 2

Message Length

PLC Decimal Value

769 — Message OK

–31999 — Message Error

Parameter Number

3 or 4

Data

Word 3

Status Word

Header Word 0

0

1

2

3

4

5

6

7

8

9

PLC request

4

–31999 20*

4096*

Drive response

3

769

20*