3-5

By default, the module is configured so that you set its IP address, subnet
mask, and gateway address using a BOOTP server. If you want to set
these features using the module’s parameters instead, you must disable
BOOTP and then set the appropriate parameters in the module using a
serial connection.

DriveExplorer (version 4.03) was used for set up examples in this
chapter. Different versions of software may differ in appearance and
procedures.

To disable the BOOTP feature

1. Set the value of Parameter 02 - [BOOTP] to Disabled.

2. Reset the module. See

Resetting the Module

section in this chapter.

After disabling the BOOTP feature, you can then configure the IP
address, subnet mask, and gateway using the module’s parameters.

To set an IP address using parameters

1. Verify that Parameter 02 - [BOOTP] is set to Disabled. This

parameter must be set to Disabled to configure the IP address using
parameters.

2. Set the value of Parameters 03 - [IP Addr Cfg 1] through 06 - [IP

Addr Cfg 4] to a unique IP address.

Figure 3.5 Example IP Address Parameter Setup Values

Setting the IP Address, Subnet Mask, and Gateway
Address

Table 3.A Parameter 02 - [BOOTP] Setup Values

Value Setting
0

Disabled

1

Enabled (Default)

Default = 0.0.0.0

255 . 255 . 255 . 255

[IP Addr Cfg 1]

[IP Addr Cfg 2]

[IP Addr Cfg 3]

[IP Addr Cfg 4]