background image

C-8

EtherNet/IP Objects

Class Code

Instances

The number of instances depends on the number of parameters in the
SCANport product. The module parameters are appended to the list of
drive parameters. The total number of parameters can be read in Instance
0, Attribute 2.

Class Attributes

Parameter Object

Hexadecimal

Decimal

0x0F

15

Instance

Description

0

Class Attributes

1

Drive Parameter 1 Attributes

n

Last Drive Parameter Attributes

n + 1

Module Parameter 1 Attributes

n + 65

Last Module Parameter Attributes

Attribute
ID

Access
Rule

Name

Data Type Description

1

Get

Revision

UINT

1

2

Get

Max Instance

UINT

Number of parameters

8

Get

Parameter
Class
Descriptor

WORD

0 = False, 1 = True
Bit 0 = Supports parameter instances
Bit 1 = Supports full attributes
Bit 2 = Must do NVS save command
Bit 3 = Parameters are stored in NVS

9

Get

Configuration
Assembly
Instance

UINT

0

10

Set

Native
Language

USINT

0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch

Advertising