Parameter value read, Plc block transfer emulation instruction data – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 147

Advertising
background image

Supported Emulated Block Transfer Commands

F-3

The following table lists the error codes.

Parameter Value Read reads the 16-bit parameter data value for the
selected parameter number.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 3 words
Drive response instruction length: 4 words

Figure F.2 Parameter Value Read Message Structure

Value

Description

0

No error occurred.

1

The service failed due to an internal reason, and the drive could not perform the
request (some messages are read only or write only).

2

The requested service is not supported.

3

An invalid value in the block transfer emulation request header word 1.

4

An invalid value in the block transfer emulation request header word 2.

5

An invalid value in the block transfer emulation request header word 1.

6

The data value is out of range.

7

There is a drive state conflict. The drive is in an incorrect state to perform the
function. The drive cannot be running when you perform certain functions.

Parameter Value Read

PLC Decimal Value

769

PLC Request

Header Word 0

Header Word 1

Header Word 2

Parameter Value or

Message Length

Drive Response

Parameter Number

3

(See Drive List)

Status Word

PLC Decimal Value

769=OK, –31999=Error

Header Word 0

Header Word 1

Data Word 3

Header Word 2

4

Parameter Number

Message Length