Nvs functions, Plc block transfer emulation instruction data, Message operation – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 160: F-16

Advertising
background image

F-16

Supported Emulated Block Transfer Commands

NVS (Non-Volatile Storage) Functions activates the specified NVS
functions.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 4 words
Drive response instruction length: 3 words

Figure F.8 NVS Functions Message Structure

Message Operation

The NVS storage function allows three different message requests:

• NVS Save saves parameter information from the working memory or

RAM to NVS Storage.

• NVS Recall retrieves the last saved data from NVS Storage and places

it in the working memory or RAM.

• NVS Default Initialize clears the RAM and NVS Storage and sets all

parameter values to default.

If an error has occurred, response word 1 returns a value of -31998.

NVS Functions

Header

Word 0

PLC Decimal Value

–31998

Header

Word 1

Header

Word 2

PLC Request

Header Word 0

Header Word 1

Header Word 2

Message Length

Message Length

PLC Decimal Value

770 — Message OK

–31998 — Message Error

0

Drive Response

4

0

Data Word 3

NVS Command

Value

NVS Command

00
01
02
03

Not Used
NVS Save
NVS Recall
NVS Default Initialize

3