Configuring the Module

3-9

A hierarchy determines the type of device with which the module
exchanges data. In a Master-Slave hierarchy, a module exchanges data
with a master, such as a scanner or bridge. In a Peer-to-Peer hierarchy, a
module exchanges data with one or more EtherNet/IP modules connected
to devices that have compatible Logic Command/Status words.

For both master-slave and peer-to-peer hierarchies, the devices
exchanging data must be on the same IP subnet. See “IP Addresses” in
the

Glossary

for information about IP subnets.

To set a Master-Slave hierarchy

1. Enable the desired I/O in Parameter 32 - [SP I/O Cfg]. Refer to

Setting the I/O Configuration

in this chapter.

2. Set the bits in Parameter 45 - [M-S Input]. This parameter

determines the data received from the master by the drive. A “1”
enables the I/O. A “0” disables the I/O.

Bit 0 is the right-most bit.

3. Set the bits in Parameter 46 - [M-S Output]. This parameter

determines the data transmitted from the drive to the scanner. A “1”
enables the I/O. A “0” disables the I/O.

Bit 0 is the right-most bit.

Selecting Master-Slave or Peer-to-Peer

Table 3.D Parameter 45 - [M-S Input] Bit Assignments

Bit

Description

0

Logic Command/Reference (Default)

1

Datalink A Input

2

Datalink B Input

3

Datalink C Input

4

Datalink D Input

5 - 7

Not Used

Table 3.E Parameter 46 - [M-S Output] Bit Assignments

Bit

Description

0

Status/Feedback (Default)

1

Datalink A Output

2

Datalink B Output

3

Datalink C Output

4

Datalink D Output

5 - 7 Not Used