D-2

Logic Command/Status Words

Logic Status Word

1336 PLUS II, 1336 PLUS, and 1305 Drives

(Continued)

Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status

Description

x Enabled

0 = Not Enabled
1 = Enabled

x

Running

0 = Not Running
1 = Running

x

Command
Direction

0 = Reverse
1 = Forward

x

Actual
Direction

0 = Reverse
1 = Forward

x

Accel

0 = Not Accelerating
1 = Accelerating

x

Decel

0 = Not Decelerating
1 = Decelerating

x

Alarm

0 = No Alarm
1 = Alarm

x

Fault

0 = No Fault
1 = Fault

x

At Speed

0 = Not At Reference
1 = At Reference

x

x

x

Local Control

000 = TB3
001 = Port 1
010 = Port 2
011 = Port 3
100 = Port 4
101 = Port 5
110 = Port 6
111 = Unused

x

x

x

x

Reference

0000 = Freq Select 1
0001 = Preset Freq 1
0010 = Preset Freq 2
0011 = Preset Freq 3
0100 = Preset Freq 4
0101 = Preset Freq 5
0110 = Preset Freq 6
0111 = Preset Freq 7
1000 = Freq Select 2
1001 = Adapter 1
1010 = Adapter 2
1011 = Adapter 3
1100 = Adapter 4
1101 = Adapter 5
1110 = Adapter 6
1111 = Jog Frequency