3-8

Configuring the Module

drive to “Adapter 2” so that the drive uses the Reference from the
module. Also, verify that the mask parameters (for example,
Parameter 92 - [Logic Mask]) in the drive are configured to receive
the desired logic from the module. Refer to the documentation for
your drive for details.

3. If you enabled one or more Datalinks, configure parameters in the

drive to determine the source and destination of data in the
Datalink(s). For example, configure the datalinks in 1305 drives by
setting Parameters 111 - [Data In A1] to 126 - [Data Out D2].
Also, ensure that the EtherNet/IP module is the only module using
the enabled Datalink(s).

4. Reset the module. See

Resetting the Module

section in this chapter.

The module is ready to receive I/O. You must now configure the module
to receive I/O from a master or peer device. Refer to

Selecting

Master-Slave or Peer-to-Peer

in this chapter. If you select a Master-Slave

hierarchy, you must also configure the master to communicate with the
module. Refer to

Chapter 4

,

Configuring the Scanner or Bridge

.

A Reference Adjustment is a percent scaling factor for the Reference
from the network and can be set from 0 to 200%. This allows the drive’s
Reference to either match the network Reference (=100%), scale below
the network Reference (<100%), or scale above the network Reference
(>100%).

If the module is receiving a Reference, adjust the scale using Parameter
47 - [Ref Adjust]
. It can be scaled between 0.00 and 200.00%. The
default is 100.00%.

The adjustment takes effect as soon as it is entered.

Setting the Reference Adjustment

!

ATTENTION: To guard against equipment damage and/or
personal injury, note that changes to Parameter 47 - [Ref
Adjust]
take effect immediately. A drive receiving its
Reference from the module will receive the newly scaled
Reference, resulting in a change of speed.