7-4

Troubleshooting

Net A Status Indicator

Status

Cause

Corrective Action

Off

The module is not
powered, the module is not
connected properly to the
network, or the module
needs an IP address.

• Securely connect the module to the drive using a

1202-Cxx Communication cable.

• Securely connect the Ethernet cable to the Ethernet

connector.

• Set a unique IP address using a BOOTP server or

by disabling BOOTP and using parameters.

• Apply power to the drive and module.

Solid Red

The module failed
duplicated IP address
detection test.

Configure the module to use a unique IP address and
cycle power.

Flashing Red

An EtherNet/IP connection
has timed out.

• Place the controller in RUN mode, or apply power to

the peer device that will send I/O.

• Check the amount of traffic on the network.

Flashing Red/
Green

The module is performing
a self-test.

No action required.

Flashing Green The module is properly

connected but is not
communicating with any
devices on the network.

• Place the controller in RUN mode, or apply power to

the peer device that will send I/O.

• Program a controller or peer device to recognize

and transmit I/O or make a messaging connection to
the module.

• Configure the module for the program in the

controller or the I/O from the peer device.

Solid Green

The module is properly
connected and
communicating on the
network.

No action required.