Resetting the module, Resetting the module -16, Section – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 42

Advertising
background image

3-16

Configuring the Module

Changes to switch settings and some module parameters require that you
reset the module before the new settings take effect. You can reset the
module by cycling power to the module or by using the following
parameter:

Set Parameter 29 - [Reset Module] to Reset Module.

When you enter 1 = Reset Module, the module will be immediately
reset. When you enter 2 = Set Defaults, the module will set all module
parameters to their factory-default settings. After performing a Set
Defaults, enter 1 = Reset Module so that the new values take effect. The
value of this parameter will be restored to 0 = Ready after the module is
reset.

Resetting the Module

!

ATTENTION: Risk of injury or equipment damage exists. If the
module is transmitting control I/O to the drive, the drive may fault when
you reset the module. Determine how your drive will respond before
resetting a connected module.

Table 3.P Parameter 29 - [Reset Module] Setup Values

Value

Description

0

Ready (Default)

1

Reset Module

2

Set Defaults

Advertising