Message operation, Example, Data file format – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 164: Fault queue size, Plc block transfer emulation instruction data, F-20

Advertising
background image

F-20

Supported Emulated Block Transfer Commands

Message Operation

Fault Queue Entry Read Full reads the contents of the fault queue
specified in word 3 of the request. The response returns the fault text
which can be ASCII text. Every two characters of text are in reverse
order. Also, the 1336 FORCE drive returns a time stamp, indicating the
day and time the fault occurred.

If an error has occurred, word 1 of the response returns a negative value.

Example

In this example, Fault Queue Entry number 3 was retrieved from a 1336
PLUS drive. The drive response returned the ASCII text Drive Reset Flt,
with each character reversed. The fault code for this example is 22.

Data File Format

* Example only — These values vary depending on parameters and products.

Fault Queue Size gets the number of fault entries allowed in the fault
queue.

PLC Block Transfer Emulation Instruction Data

PLC request instruction length: 3 words
Drive response instruction length: 4 words

0

1

2

3

4

5

6

7

8

9

PLC request

3

1792

3*

Drive response 12

1792

3*

29252* 20313* 8293* 25938* 25971* 8308* 27718*

8303* 22*

Drive response \00\0C \07\00 \03\00 r D

v i

e

e R

e s

t

l F

t

\00\16

Fault Queue Size