Troubleshooting

PORT Status Indicator

Status

Cause

Corrective Action

Off

The module is not powered or
is not connected properly to
the drive.

• Securely connect the module to the drive using a

1202-Cxx Communication cable.

• Apply power to the module.

Flashing Red

The module is not receiving a
ping message from the drive.

• Verify that the 1202-Cxx Communication cable is

securely connected.

• Cycle power to the drive and/or module.

Solid Red

The drive has refused an
I/O connection from the
module.

Another SCANport peripheral
is using the same SCANport
port as the module.

Important: Cycle power to the drive and/or module
after making any of the following corrections:

• Verify that all 1202-Cxx cables are securely

connected and not damaged. Replace cables if
necessary.

• Verify that the SCANport Host supports Datalinks.
• Configure the module to use a Datalink that is not

already being used by another peripheral.

Flashing Green The module is establishing an

I/O connection to the drive.

No action required. Normal behavior if no SCANport
I/O is enabled.

Solid Green

The module is properly
connected and is
communicating with the drive.

No action required.

Flashing Red/
Green

The module is performing a
self-test.

No action required.