Using reference/feedback, Using reference/feedback -4 – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 56

Advertising
background image

5-4

Using I/O Messaging

When enabled, Reference begins at word 1 (16-bit) in the Output image
and Feedback begins at word 3 in the Input image. The Reference (16
bits) is produced by the controller and consumed by the module. The
Feedback (16 bits) is produced by the module and consumed by the
controller.

The Reference value is a scaled value; it is not an engineering value. For
example, in 1305 drives, the Reference is scaled based on the value of
Parameter 19 - [Maximum Freq] where “32,767” equals the Parameter
19 frequency value, and “0” equals 0 Hz.

Table 5.A

shows example

References and their results on a 1305 drive that has its Parameter 19 -
[Maximum Freq]
set to 60 Hz (default).

For Reference/Feedback details about other SCANport products, refer to
their respective User Manuals.

Using Reference/Feedback

Table 5.A Example Speed Reference and Feedback for a 1305 Drive

Reference
Value

Scale

Output Speed

Feedback
Value

Percent

Value

32767

100%

60 Hz

60 Hz

32767

16384

50%

30 Hz

30 Hz

16384

8192

25%

15 Hz

15 Hz

8192

0

0%

0 Hz

0 Hz

0