Net b status indicator, Net b status indicator -5 – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 85

Advertising
background image

Troubleshooting

7-5

Net B Status Indicator

Status

Cause

Corrective Action

Off

The module is not powered
or is not transmitting on the
EtherNet/IP network.

If Net A is off:

• Securely connect the module to the drive using a

1202-Cxx Communication cable.

• Securely connect the Ethernet cable to the Ethernet

connector.

• Set a unique IP address using a BOOTP server or

by disabling BOOTP and using parameters.

If Net A is solid red:

• Configure the module to use a unique IP address

and cycle power.

If Net A is flashing red/green or red:

• Check the IP address in the module and scanner.
• Ping the module.
Normal condition if the module is idle.

Flashing Green

The module is transmitting
on the EtherNet/IP
network.

No action required.

Advertising