Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 104

Advertising
background image

B-4

Module Parameters

28

[EN Rate Act]
Displays the data rate actually used by the
module.

Default:

0 = No Link

Values

0 = No Link
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half

Type:

Read Only

29

[Reset Module]
No action if set to “Ready.” Resets the module if
set to “Reset Module.” Restores the module to its
factory default settings if set to “Set Defaults.” This
parameter is a command. It will be reset to
“Ready” after the command has been performed.

Default:

0 = Ready

Values

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required:

No

30

[Comm Flt Action]
Sets the action that the module will take if it
detects a network failure. This setting is effective
only if I/O that controls the drive is transmitted
through the module.

Default:

0 = Fault

Values:

0 = Fault
1 = Zero Data
2 = Hold Last
3 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

31

[Idle Flt Action]
Sets the action that the module and drive take if
the module detects that the scanner is idle
because the controller was switched to program
mode. This setting is effective only if I/O that
controls the drive is transmitted through the
module.

Default:

0 = Fault

Values:

0 = Fault
1 = Zero Data
2 = Hold Last
3 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. If the module is
transmitting I/O that controls the drive, the drive may fault when you reset the
module. Determine how your drive will respond before resetting a connected
module.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 30 - [Comm
Flt Action]
lets you determine the action of the module and connected drive if the
communications are disrupted. By default, this parameter faults the drive. You can
set this parameter so that the drive continues to run. Precautions should be taken
to ensure that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected cable).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 31 - [Idle Flt
Action]
lets you determine the action of the module and connected drive if the
scanner is idle. By default, this parameter faults the drive. You can set this
parameter so that the drive continues to run. Precautions should be taken to
ensure that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a faulted controller).

Advertising