B-6 module parameters – Rockwell Automation 1203-EN1 EtherNet/IP-to-SCANport Module User Manual

Page 106

Advertising
background image

B-6

Module Parameters

36
37
38
39
40
41
42
43

[Flt Cfg A1 In]
[Flt Cfg A2 In]
[Flt Cfg B1 In]
[Flt Cfg B2 In]
[Flt Cfg C1 In]
[Flt Cfg C2 In]
[Flt Cfg D1 In]
[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:

• Parameter 30 - [Comm Flt Action] is set to

“Send Flt Cfg” and communications are
disrupted.

• Parameter 31 - [Idle Flt Action] is set to “Send

Flt Cfg” and the scanner is idle.

• Parameter 51 - [Peer Flt Action] is set to “Send

Flt Cfg” and communications are disrupted.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read/Write

Reset Required:

No

44

[Serial Port Rate]
Sets the data rate of the serial port.

Default:

2 = 9600 bps

Values:

0 = 2400 bps
1 = 4800 bps
2 = 9600 bps
3 = 19.2 Kbps
4 = 38.4 Kbps

Type:

Read/Write

Reset Required:

Yes

45

[M-S Input]
Sets the Master-Slave input data. This data is
produced by the scanner and consumed by the
module.

Default:

xxx0 0001

Bit Values:

0 = I/O disabled
1 = I/O enabled

Type:

Read/Write

Reset Required:

Yes

Bit Definitions
0 = Cmd/Ref
1 = Datalink A Input
2 = Datalink B Input
3 = Datalink C Input
4 = Datalink D Input
5 = Not Used
6 = Not Used
7 = Not Used

Parameter
No. Name and Description

Details

Bit

Default

1

0

0

0

0

x x

x

0

1

2

3

4

5

7 6