MicroLogix 1500 Example Ladder Programs
6-21
The write message instruction on rung 0004 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:
The format of the command data is:
Data Word
Example Value
Description
N7:120
15
PowerFlex 70 node address
N7:121
6
Function Code – Write Single Registers
N7:122
1099
Starting Register Address (41100)
N7:123
1
Number of registers to write
N7:124
111
Parameter 100 write data