Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 101

Advertising
background image

MicroLogix 1500 Example Ladder Programs

6-21

The write message instruction on rung 0004 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:

The format of the command data is:

Data Word

Example Value

Description

N7:120

15

PowerFlex 70 node address

N7:121

6

Function Code – Write Single Registers

N7:122

1099

Starting Register Address (41100)

N7:123

1

Number of registers to write

N7:124

111

Parameter 100 write data