MicroLogix 1500 Example Ladder Programs
Figure 6.1 Example MicroLogix 1500 Single Mode System Arrangement
PowerFlex 40 Drive Settings
The PowerFlex 40 drives used in the example program have the
following parameter settings:
1769-SM2 Module Settings
The 1769-SM2 module used in the example program has the following
switch settings:
Parameter
Setting
P036 - [Start Source]
5 (Comm Port)
P038 - [Speed Reference]
5 (Comm Port)
A103 - [Comm Data Rate]
4 (19.2K)
A104 - [Comm Node Addr]
100
A107 - [Comm Format]
0 (RTU 8-N-1)
Switch
Setting
Configuration Mode Switch (SW1)
CONT position
Operating Mode Switch (SW2)
1X (Single) position
PowerFlex 4/40 Drives
CH1
CH2
CH3
MicroLogix 1500 Controller
C
H
1
C
H
2
C
H
3
DSI