Powerflex 40 drive settings, 1769-sm2 module settings, Channel – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 82: Figure 6.1

Advertising
background image

6-2

MicroLogix 1500 Example Ladder Programs

Figure 6.1 Example MicroLogix 1500 Single Mode System Arrangement

PowerFlex 40 Drive Settings

The PowerFlex 40 drives used in the example program have the
following parameter settings:

1769-SM2 Module Settings

The 1769-SM2 module used in the example program has the following
switch settings:

Parameter

Setting

P036 - [Start Source]

5 (Comm Port)

P038 - [Speed Reference]

5 (Comm Port)

A103 - [Comm Data Rate]

4 (19.2K)

A104 - [Comm Node Addr]

100

A107 - [Comm Format]

0 (RTU 8-N-1)

Switch

Setting

Configuration Mode Switch (SW1)

CONT position

Operating Mode Switch (SW2)

1X (Single) position

PowerFlex 4/40 Drives

CH1

CH2

CH3

MicroLogix 1500 Controller

C

H

1

C

H

2

C

H

3

DSI