Formulas for converting, Common services, Object specific services – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 183: R to, Dsi parameter object

Advertising
background image

CIP/DSI Objects

C-13

Descriptor Attributes (Continued)

Formulas for Converting

Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10

Decimal Places

)

Internal Value = ((Display Value x Divisor x 10

Decimal Places

) / (Multiplier x Base)) - Offset

Common Services

Object Specific Services

The table below lists the parameters for the Get_Attributes_Scattered
and Set_Attributes_Scattered object-specific service:

Important: The STRUCT may repeat up to 55 times in a single message.

DSI Parameter Object

(Continued)

Bit

Name

Description

19

Parameter Exists

Reserved

20

Not Used

Reserved

21

Formula Links

Reserved

22

Access Level (Bit 1)

Reserved

23

Access Level (Bit 2)

Reserved

24

Access Level (Bit 3)

Reserved

25

Writable ENUM

Reserved

26

Not a Link Source

0 = Parameter can be a source for a link
1 = Parameter cannot be a source for a link

27

Enhanced Bit ENUM

Reserved

28

Enhanced ENUM

Reserved

29

Not Used

Reserved

30

Not Used

Reserved

31

Not Used

Reserved

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single

Service Code

Service Name

0x32

Get_Attributes_Scattered

(1)

(1)

The instance and attribute are ignored for these services.

0x34

Set_Attributes_Scattered

(1)

Name

Data Type

Description

Scattered Parameters STRUCT of

Parameter Number

WORD

Parameter to read or write

Parameter Value

WORD

Parameter value to read or write (zero when reading)

Advertising