Modbus rtu master operation messages, Modbus rtu master operation messages -9 – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 73

Advertising
background image

Understanding Explicit Messaging

5-9

In Multi-Drive mode, any channel can be configured for Modbus RTU
Master operation to communicate with a variety of Rockwell
Automation or 3rd Party RTU Slave devices, such as PowerFlex 7-Class
drives with 20-COMM-H adapters. In the Multi-Drive ladder examples
provided in this manual, CH3 is used to communicate with a PowerFlex
70 drive.

The following Modbus Function Codes are supported:

The format of the Modbus command message data is:

The format of the Modbus response message data is:

The format of the message instruction is different for Modbus RTU
Master operation messaging. For RSLogix 500, format each message as
shown in

Figure 5.7

and see

Table 5.D

for a description of the data

required in each field. For RSLogix 5000, format each message as shown
in

Figure 5.8

and see

Table 5.E

.

Modbus RTU Master Operation Messages

Function
Code

Name

Maximum
Bits/Word

Function
Code

Name

Maximum
Bits/Word

01

Read Coils

512

05

Write Single Coil

n/a

02

Read Discrete Inputs

512

06

Write Single Register

n/a

03

Read Holding Registers 32

15

Write Multiple Coils

512

04

Read Input Registers

32

16

Write Multiple Registers 512

Word

Name

Description

1

RTU Slave Address

The node address of the Modbus RTU Slave.

2

Function Code

The Modbus Function Code to perform.

3

Starting Address

The starting coil/register address in the Slave device.

4

Number of bits/words

The number of coils/registers to read/write.

5+

Data Words

Only used for write messages and contains the data
to be written.

Word

Name

Description

1+

Data Words

Only used for read messages and contains the data
that was read.