Powerflex 40 settings, 1769-sm2 settings, Channel – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 104: Figure 7.1

Advertising
background image

7-2

CompactLogix Example Ladder Programs

Figure 7.1 Example CompactLogix Single Mode System Arrangement

PowerFlex 40 Settings

The PowerFlex 40 drives used in the example program have the
following parameter settings:

1769-SM2 Settings

The 1769-SM2 module used in the example program has the following
switch settings:

Parameter

Setting

P036 - [Start Source]

5 (Comm Port)

P038 - [Speed Reference]

5 (Comm Port)

A103 - [Comm Data Rate]

4 (19.2K)

A104 - [Comm Node Addr]

100

A107 - [Comm Format]

0 (RTU 8-N-1)

Switch

Setting

Configuration Mode Switch (SW1)

CONT position

Operating Mode Switch (SW2)

1X (Single) position

PowerFlex 4/40 Drives

CH1

CH2

CH3

CompactLogix Controller

DSI

MODULE

CH1

CH2

CH3

C

H

1

C

H

2

C

H

3

Advertising