3-22

Configuring the Module

The adapter can be flash updated over the network (via EtherNet/IP
using DriveExplorer Full only) or serially through a direct connection
from a computer to the drive using a 1203-USB converter or
22-SCM-232 serial converter module (firmware v2.005 or higher).

Not all flash methods (DriveExplorer Lite/Full, ControlFLASH or
HyperTerminal) can be used successfully in all cases. Depending on the
controller and the operating mode of the 1769-SM2 module, these flash
methods can be used:

Important: In ALL cases, the controller must be set to Program

mode—not the Run mode—to successfully flash the
1769-SM2 module.

To obtain a flash update for this adapter, go to

http://www.ab.com/

support/abdrives/webupdate

. This site contains all firmware update files

and associated Release Notes that describe firmware update
enhancements/anomalies, how to determine the existing firmware
version, and how to flash update using DriveExplorer Lite/Full,
ControlFLASH or HyperTerminal.

Flash Updating the Module

Controller

1769-SM2
Operating Mode

Flash Methods to Use

MicroLogix 1500

Single

DriveExplorer Lite/Full, ControlFLASH or
HyperTerminal via a 1203-USB or 22-SCM-232
converter

Multi-Drive

Must first change the 1769-SM2 operating mode
from Multi-Drive to Single before flashing. Then
flash using any of the methods listed in the row
above.

CompactLogix

Single

DriveExplorer Lite/Full, ControlFLASH or
HyperTerminal via a 1203-USB or
22-SCM-232 converter

ControlFLASH via the CompactLogix
controller backplane

Multi-Drive

ControlFLASH via the CompactLogix controller
backplane