3-14

Configuring the Module

The I/O configuration sets the number of drives that are connected to
each channel. When the 1769-SM2 module is used in Single mode
(Operating Mode Switch SW2 set to “1X”), only one PowerFlex 4-Class
drive can be connected to each channel and module Parameters 07 -
[DSI I/O Cfg 1]
, 22 - [DSI I/O Cfg 2], and 37 - [DSI I/O Cfg 3] have no
effect. When the module is used in Multi-Drive mode (Operating Mode
Switch set to “5X”), up to five PowerFlex 4-Class drives can be
connected to each channel. When a channel is selected for Modbus RTU
Master operation, up to 31 devices can be connected.

1. Set the value in Parameters 07 - [DSI I/O Cfg 1], 22 - [DSI I/O Cfg

2], and 37 - [DSI I/O Cfg 3] to respectively configure each module
channel for the number of drives being used in Multi-Drive mode.

Figure 3.14 Example I/O Cfg Screen for CH1 Drive(s) in Multi-Drive Mode

Each drive (Drive 0, Drive 1, etc.) on the node must be assigned a
node address [see

Setting Drive Node Addresses (Multi-Drive Mode

Only) on page 3-16

]. For more information on Multi-Drive mode and

RTU Master mode, refer to the Multi-Drive Mode section in the
chapter corresponding to your controller type:

Chapter 6

,

MicroLogix 1500 Example Ladder Programs

Chapter 7

,

CompactLogix Example Ladder Programs

Chapter 8

,

ControlLogix w/1769-ADN DeviceNet Example

Ladder Program

2. Configure the parameters in each enabled drive to accept the Logic

Command and Reference from the 1769-SM2 module. For example,
set PowerFlex 4/40/400 drive Parameters 36 - [Start Source] and 38 -
[Speed Reference] to “5” (Comm Port) so that the drive uses the
Reference from the 1769-SM2 module.

3. Reset the module (see

Resetting the Module on page 3-20

).

Setting the I/O Configuration (Multi-Drive Mode Only)

Value Description

Mode Switch Position

Single Multi-Drive

0

Drive 0 (Default)

1

Drives 0…1

No

t Applicab

le

2

Drives 0…2

3

Drives 0…3

4

Drives 0…4

5

RTU Master

DSI I/O Cfg 1

Parameter:

#

007

Drives 0…4

4

VALUE

LIMITS