2-10

Installing the Module

8. Connect the 1769-SM2 module and adjacent modules together by

locking (fully left) the bus levers on the 1769-SM2 module and the
right-side adjacent module.

9. Replace the mounting screws (or snap the module onto the DIN rail).

10. Plug the appropriate communications cable into its respective port on

the 1769-SM2 module.

11. Restore 1769-SM2 module configuration using an appropriate

configuration tool.

NOTE: For Single or Multi-Drive mode, there is a maximum cable
distance limit per channel. See

DSI Cable Requirements on page A-2

for

more information.

For network wiring diagram examples, see the following figures:

Single Mode

When the 1769-SM2 module is operated in Single drive mode, each
drive is directly connected to a channel port (CH1, CH2 or CH3) on the
module. Use either a 22-RJ45CBL-C20 communications cable for each
channel or AK-U0-RJ45-TB2P terminal block connectors and twisted
pair network wiring (Belden No. 3105A or equivalent).

Important: When connecting a drive to the channel port using

AK-U0-RJ45-TB2P terminal block connectors and twisted
pair network wiring, the following drive parameters MUST
be configured to the settings shown so that the 1769-SM2
module will communicate with the drive:

Changes to these drive parameters require the drive to be
reset for the new settings to take effect.

Connecting Drive(s) to the Module

1769-SM2 Operating Mode

Network Wiring
Diagram Example…

Single mode (Default)

Figure 1.2

Multi-Drive mode

Figure 1.3

Multi-Drive mode with Modbus RTU Master

Figure 1.4

Drive Parameter

Setting

A103 - [Comm Data Rate]

“4” (19.2K)

A107 - [Comm Format]

“0” (RTU 8-N-1)