Troubleshooting

The MODULE status indicator is a bicolor red and green LED.

MODULE Status Indicator

Status

Cause

Corrective Action

Off

The module is not powered.

Apply power to the module.

Flashing
Red

The module’s configuration data
is not valid.

Change the controller configuration
data to valid settings.

Reset the module parameters to
their default settings, and then reset
the module.

Steady Red

The module is unable to
establish communication with the
controller.

Cycle power to the controller.

Flashing
Green

The module is establishing
communications with the
controller.

Normal behavior -- no action required.

Steady
Green

The module has established
communications with the
controller.

Normal behavior -- no action required.

Flashing
Red/Green

The module is in boot mode.

Flash download the application code to
the module.