Using logic command/status, Using reference/feedback – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 64

Advertising
background image

4-4

Understanding the I/O Image

The Logic Command is a 16-bit word of control data produced by the
controller and consumed by the 1769-SM2 module. The Logic Status is a
16-bit word of status data produced by the 1769-SM2 module and
consumed by the controller.

This manual contains the bit definitions for compatible products
available at the time of publication in

Appendix D

. For other products,

refer to their documentation.

The Reference (16 bits) is produced by the controller and consumed by
the 1769-SM2 module. The Feedback (16 bits) is produced by the
1769-SM2 module and consumed by the controller.

Valid Reference/Feedback values for PowerFlex 4-Class drives are:

Using Logic Command/Status

Using Reference/Feedback

Size

Drive

Valid Values

(1)

(1)

The Reference/Feedback for a PowerFlex 4-Class drive is set in Hz and
not in engineering units like PowerFlex 7-Class drives. For example,
“300” equates to 30.0 Hz (the decimal point is always implied) for all
PowerFlex 4-Class drives—except PowerFlex 400 for which “3000”
equates to 30.00 Hz. In all cases, a minus value equates to reverse
motor direction, and a plus value equates to forward motor direction.

16-bit

PowerFlex 4

-240.0…240.0 Hz

PowerFlex 4M
PowerFlex 40

-400.0…400.0 Hz

PowerFlex 40P
PowerFlex 400

-320.00…320.00 Hz