CompactLogix Example Ladder Programs

7-11

Figure 7.4 Example CompactLogix Multi-Drive Mode System Arrangement

PowerFlex 40 Settings

The PowerFlex 40 drives used in the example program have the
following parameter settings:

PowerFlex 70 Setting

The PowerFlex 70 drive used in the example program has the following
parameter setting:

Up to 5 PowerFlex 4/40 Drives

CH1

CH2

CH3

CompactLogix Controller

Up to 5 PowerFlex 4/40 Drives

PowerFlex 70 Drive
with 20-COMM-H Adapter

DSI

MODULE

CH1

CH2

CH3

C

H

1

C

H

2

C

H

3

Parameter

Setting

P036 - [Start Source]

5 (Comm Port)

P038 - [Speed Reference]

5 (Comm Port)

A103 - [Comm Data Rate]

4 (19.2K)

A104 - [Comm Node Addr]

100…104

A107 - [Comm Format]

0 (RTU 8-N-1)

Parameter

Setting

90 - [Speed Ref A Sel]

22(DPI Port 5)