Setting the rtu rx delay time, Setting the rtu tx delay time – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 56

Advertising
background image

3-18

Configuring the Module

Figure 3.18 Example RTU Format HIM Screen for CH1 Drives

2. Reset the module (see

Resetting the Module on page 3-20

).

Setting the RTU Rx Delay Time

1. Set the values of Parameters 16 - [RTU Rx Delay 1], 31- [RTU Rx

Delay 2], and 46 - [RTU Rx Delay 3] to establish the inter-character
delay time that detects the end of a receive packet for the respective
channel.

Figure 3.19 Example RTU Rx Delay HIM Screen for CH1 Drives

2. Reset the module (see

Resetting the Module on page 3-20

).

Setting the RTU Tx Delay Time

1. Set the values of Parameters 17 - [RTU Tx Delay 1], 32- [RTU Tx

Delay 2], and 47 - [RTU Tx Delay 3] to establish the inter-frame
delay time that delays the sending of a transmit packet for the
respective channel.

Value

Format

0

8-N-1 (default)

1

8-E-1

2

8-O-1

3

8-N-2

4

8-E-2

5

8-O-2

RTU Format 1

Parameter:

#

015

0

VALUE

LIMITS

SEL

Default:

0 milliseconds

Minimum: 0 milliseconds
Maximum: 500 milliseconds

RTU Rx Delay 1

Parameter:

#

016

0

VALUE

LIMITS

SEL

TIP: If the Modbus RTU slave is a PowerFlex 4-Class drive, set the
value of [RTU Rx Delay x] to 2 milliseconds when the value of
[RTU Baud Rate x] is 19200.

Advertising