This chapter provides instructions and information for setting the
parameters in the 1769-SM2 module.

For a list of parameters, refer to

Appendix B

,

Module Parameters

. For

definitions of terms in this chapter, refer to the

Glossary

.

Single Mode

When the module is in Single mode, the I/O image is comprised of a
maximum of 7 words (

Table 3.A

).

Table 3.A I/O Image Table for Single Mode

Topic

Page

Determining I/O Image Size

3-1

Configuration Tools

3-2

Configuration Methods

3-3

Controller Mode

3-3

Parameter Mode

3-12

Using the Optional, External PowerFlex 4-Class HIM

3-13

Setting the I/O Configuration (Multi-Drive Mode Only)

3-14

Setting an Idle Action (Single and Multi-Drive Mode)

3-15

Setting Drive Node Addresses (Multi-Drive Mode Only)

3-16

Configuring the Modbus RTU Master Parameters

3-17

Resetting the Module

3-20

Viewing the Module Status Using Parameters

3-21

Flash Updating the Module

3-22

Determining I/O Image Size

Output Image

Input Image

Word

CH1

CH2

CH3

Module Control Word

Module Status Word

0

Logic Command

Logic Status

1

3

5

Reference

Feedback

2

4

6

TIP: When using Single mode, it is recommended to set the I/O size to
7 Input words and 7 Output words. This accommodates one drive per
channel, even if a channel is left unused for future use.