N in, Figure 5.2, And see – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 67: Table 5.b
Understanding Explicit Messaging
5-3
Figure 5.2 RSLogix 5000 Explicit Message Setup Screen
Table 5.B RSLogix 5000 Explicit Message Configuration Data
Configuration Tab
Description
Message Type
Always use “CIP Generic.”
Service Type
The service is used to read/write a parameter value.
Service Code
Code for the requested service.
Class
Class ID for the DSI Parameter Object.
Instance
Instance number in the Class.
Attribute
Attribute number of the Instance.
Source Element
Source of the request service data.
Source Length
Length of the request service data.
Destination
Location where the response service data (if any) is stored.
Communication Tab
Description
Path
Format is <Name of Module>,2,n — where “n” equals the
channel number (1…3) on the 1769-SM2.
Tag Tab
Description
Name
The name for the message instruction.