Setting the rtu message timeout – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 57

Advertising
background image

Configuring the Module

3-19

Figure 3.20 Example RTU Tx Delay HIM Screen for CH1 Drives

2. Reset the module (see

Resetting the Module on page 3-20

).

Setting the RTU Message Timeout

1. Set the values of Parameters 18 - [RTU MsgTimeout 1], 33- [RTU

MsgTimeout 2], and 48 - [RTU MsgTimeout 3] to establish the
amount of time that the module will wait for a response from the
respective channel’s drives.

Figure 3.21 Example RTU MsgTimeout HIM Screen for CH1 Drives

Important: The RTU Message Timeout value must be considered

when determining the timeout values in the slave nodes.
For example, if five RTU messages are being sent to a
slave node and the slave is powered down, the overall
network cycle time can increase by as much as 10
seconds (5 messages x 2 seconds timeout for each slave
node).

2. Reset the module (see

Resetting the Module on page 3-20

).

Default:

0 milliseconds

Minimum: 0 milliseconds
Maximum: 500 milliseconds

RTU Tx Delay 1

Parameter:

#

017

0

VALUE

LIMITS

SEL

TIP: If the Modbus RTU slave is a PowerFlex 4-Class drive, set the
value of [RTU Tx Delay x] to 8 milliseconds when the value of
[RTU Baud Rate x] is 19200.

Default:

2 seconds

Minimum: 0 seconds
Maximum: 60 seconds

RTU MsgTimeout 1

Parameter:

#

018

2

VALUE

LIMITS

SEL

TIP: When configured for RTU Master operation, the RTU Slave
addresses do not get assigned with parameter values. The Slave
address is contained in the message data as described in

Chapter 5

.

Advertising