6-4

MicroLogix 1500 Example Ladder Programs

MicroLogix 1500 Example Program

Figure 6.2 Example MicroLogix 1500 Single Mode Ladder Logic Main Routine

MicroLogix 1500 w/ 1769-SM2 in Single mode

In this Single mode example program, the channels are utilized as follows:

Channel 1 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)

Channel 2 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)

Channel 3 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)

This rung enables the 1769-SM2 to send the Channel 1 Logic Command and Reference words to the drive.

0000

O:1

0

1769-SM2

Channel 1

Enable

Channel 1 Subroutine

0001

JSR

Jump To Subroutine

SBR File Number

U:3

JSR

This rung enables the 1769-SM2 to send the Channel 2 Logic Command and Reference words to the drive.

0002

O:1

1

1769-SM2

Channel 2

Enable

Channel 2 Subroutine

0003

JSR

Jump To Subroutine

SBR File Number

U:4

JSR

This rung enables the 1769-SM2 to send the Channel 3 Logic Command and Reference words to the drive.

0004

O:1

2

1769-SM2

Channel 3

Enable

Channel 3 Subroutine

0005

JSR

Jump To Subroutine

SBR File Number

U:5

JSR

0006

I:1

0

1769-SM2

CH1

Drive 0

Logic Sts Valid

I:1

5

1769-SM2

CH2

Drive 0

Logic Sts Valid

I:1

10

1769-SM2

CH3

Drive 0

Logic Sts Valid

B3:0

0

1769-SM2

Input Data

Valid

0007

I:1

15

1769-SM2

1769-SM2

Config Data

Valid

B3:0

1

1769-SM2

Config Data

Error

0008

END