ControlLogix w/1769-ADN DeviceNet Example Ladder Program

8-15

Figure 8.19 Example ControlLogix Ladder Logic CH1 Subroutine

1769-SM2 Channel 1 Subroutine

The following rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual

for additional information about the Logic Status word.

0

SM2_Input_Data[3].0

CH1_Ready

i

1

SM2_Input_Data[3].1

CH1_Active

2

SM2_Input_Data[3].3

CH1_Forward

3

SM2_Input_Data[3].7

CH1_Fault

4

SM2_Input_Data[3].8

CH1_At_Speed

This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the

drive, so a displayed value of "300" equates to 30.0 Hz.

5

Move

Source SM2_Input_Data[4]

100

Dest

CH1_Feedback

100

MOV

The following rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user

manual for additional information about the Logic Command word.

6

CH1_Stop

SM2_Output_Data[1].0

i

This rung unlatches the contact that turns on the Start command when the drive is not communicating with the 1769-SM2.

This prevents the drive from immediately starting when communications are restored. If an immediate start is desired for an

application, this rung could be deleted.

7

/

CH1_Valid_Data

<SM2_Input_Data[2].0>

U

CH1_Start

8

CH1_Start

SM2_Output_Data[1].1

9

CH1_Jog

SM2_Output_Data[1].2

10

CH1_Clear_Fault

SM2_Output_Data[1].3