Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 99

Advertising
background image

MicroLogix 1500 Example Ladder Programs

6-19

The Logic Command/Reference write message instruction on rung 0000
is configured as follows:

Figure 6.7 Example MicroLogix 1500 Modbus RTU Ladder Logic CH3 Subroutine (Continued)

Write Parameter 100 [Jog Frequency] (written 1x per request).

N7:120 = Slave Address ("15" is the 20-COMM-H address)

N7:121 = Function Code ("6" is Write Single Register command)

N7:122 = Starting Address ("1099" = 4x1100)

N7:123 = Length ("1")

N7:124 = Pr. 100 [Jog Frequency] Write Value

0004

B3:30

2

CH3

Write

Pr.100

EN

DN

ER

MSG

Read/Write Message

MSG File

MG9:22

Setup Screen

MSG

Read Parameter 100 [Jog Frequency] (read 1x per request).

N7:130 = Slave Address ("15" is the 20-COMM-H address)

N7:131 = Function Code ("3" is Read Holding Register command)

N7:132 = Starting Address ("1099" = 4x1100)

N7:133 = Length ("1")

The response data is stored in:

N7:134 = Pr. 100 [Jog Frequency] Read Value

0005

B3:30

3

CH3

Read

Pr.100

EN

DN

ER

MSG

Read/Write Message

MSG File

MG9:23

Setup Screen

MSG

0006

RET

Return

RET

0007

END

Advertising