Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 102

Advertising
background image

6-22

MicroLogix 1500 Example Ladder Programs

The read message instruction on rung 0005 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:

The format of the command data is:

The format of the response data is:

For additional information about Modbus RTU Master messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual
, publication 20COMM-UM009.

Data Word

Example Value

Description

N7:130

15

PowerFlex 70 node address

N7:131

3

Function Code – Read Holding Registers

N7:132

1099

Starting Register Address (41100)

N7:133

1

Number of registers to read

Data Word

Example Value

Description

N7:134

111

Parameter 100 read data