Chapter 5, Understanding explicit messaging, 5understanding explicit messaging – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual
Page 65
Chapter
5
Understanding Explicit Messaging
This chapter provides information about explicit messaging.
Explicit messaging is used to read/write data that is not part of the
module’s I/O Image (
•
Reading/writing drive parameters.
•
Operating as a Modbus RTU Master and initiating Request/Response
messages to Modbus RTU Slave devices, such as PowerFlex 7-Class
drives with 20-COMM-H adapters.
The following table shows various products that can be used with the
1769-SM2 module and whether they support explicit messaging:
Contact your local Rockwell Automation, Inc. representative for
inquiries about the explicit message capabilities of products not
specified above.
Topic
Page
Modbus RTU Master Operation Messages
Products
Supports Explicit Messaging
Yes
No
MicroLogix 1500 LRP Series A and B, and
LSP processors
✔
MicroLogix 1500 LRP Series C (or newer) and
RSLogix 500 v6.30 (or higher)
Important: This LRP processor supports messaging
only for the first two I/O modules capable of messaging.
✔
RSLogix 500 versions prior to v6.30
✔
Enhanced CompactLogix processors such as the -L31,
-L32E, and -L35E
✔
CompactLogix -L20 and -L30 processors
✔
1769-ADN DeviceNet adapter (see documentation for
possible future explicit messaging support)
✔
!
ATTENTION: Hazard of equipment damage exists. If Explicit
Messages are programmed to write parameter data to Non-Volatile
Storage (NVS) frequently, the NVS will quickly exceed its life cycle
and cause the drive to malfunction. Do not create a program that
frequently uses Explicit Messages to write parameter data to NVS.