Chapter 5, Understanding explicit messaging, 5understanding explicit messaging – Rockwell Automation 1769-SM2 Compact I/O DSI/Modbus Communication Module User Manual

Page 65

Advertising
background image

Chapter

5

Understanding Explicit Messaging

This chapter provides information about explicit messaging.

Explicit messaging is used to read/write data that is not part of the
module’s I/O Image (

Chapter 4

), such as:

Reading/writing drive parameters.

Operating as a Modbus RTU Master and initiating Request/Response
messages to Modbus RTU Slave devices, such as PowerFlex 7-Class
drives with 20-COMM-H adapters.

The following table shows various products that can be used with the
1769-SM2 module and whether they support explicit messaging:

Contact your local Rockwell Automation, Inc. representative for
inquiries about the explicit message capabilities of products not
specified above.

Topic

Page

Formatting Explicit Messages

5-2

Modbus RTU Master Operation Messages

5-9

Products

Supports Explicit Messaging

Yes

No

MicroLogix 1500 LRP Series A and B, and
LSP processors

MicroLogix 1500 LRP Series C (or newer) and
RSLogix 500 v6.30 (or higher)

Important: This LRP processor supports messaging
only for the first two I/O modules capable of messaging.

RSLogix 500 versions prior to v6.30

Enhanced CompactLogix processors such as the -L31,
-L32E, and -L35E

CompactLogix -L20 and -L30 processors

1769-ADN DeviceNet adapter (see documentation for
possible future explicit messaging support)

!

ATTENTION: Hazard of equipment damage exists. If Explicit
Messages are programmed to write parameter data to Non-Volatile
Storage (NVS) frequently, the NVS will quickly exceed its life cycle
and cause the drive to malfunction. Do not create a program that
frequently uses Explicit Messages to write parameter data to NVS.

Advertising